Preparing for Installation
This section contains the following topics:
Installation Warnings and Guidelines
Note |
Before you install, operate, or service a Cisco CSP 5400, review the Regulatory Compliance and Safety Information for Cisco CSP 5400 for important safety information. |
Warning |
IMPORTANT SAFETY INSTRUCTIONS This warning symbol means danger. You are in a situation that could cause bodily injury. Before you work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing accidents. Use the statement number provided at the end of each warning to locate its translation in the translated safety warnings that accompanied this device. Statement 1071 |
Warning |
To prevent the system from overheating, do not operate it in an area that exceeds the maximum recommended ambient temperature of: 35° C (95° F). Statement 1047 |
Warning |
The plug-socket combination must be accessible at all times, because it serves as the main disconnecting device. Statement 1019 |
Warning |
This product relies on the building’s installation for short-circuit (overcurrent) protection. Ensure that the protective device is rated not greater than: 250 V, 15 A. Statement 1005 |
Warning |
Installation of the equipment must comply with local and national electrical codes. Statement 1074 |
Warning |
This unit is intended for installation in restricted access areas. A restricted access area can be accessed only through the use of a special tool, lock, and key, or other means of security. Statement 1017 |
Caution |
To ensure proper airflow it is necessary to rack the Cisco CSP 5400s using rail kits. Physically placing the units on top of one another or “stacking” without the use of the rail kits blocks the air vents on top of the Cisco CSP 5400s, which could result in overheating, higher fan speeds, and higher power consumption. We recommend that you mount your Cisco CSP 5400s on rail kits when you are installing them into the rack because these rails provide the minimal spacing required between the Cisco CSP 5400. No additional spacing between the Cisco CSP 5400s is required when you mount the units using rail kits. |
Caution |
Avoid uninterruptible power supply (UPS) types that use ferroresonant technology. These UPS types can become unstable with systems such as the Cisco UCS, which can have substantial current draw fluctuations from fluctuating data traffic patterns. |
When you are installing a Cisco CSP 5400, use the following guidelines:
-
Plan your site configuration and prepare the site before installing the Cisco CSP 5400. See the Cisco UCS Site Preparation Guide for the recommended site planning tasks.
-
Ensure that there is adequate space around the Cisco CSP 5400 to allow for accessing the Cisco CSP 5400 and for adequate airflow. The airflow in this Cisco CSP 5400 is from front to back.
-
Ensure that the air-conditioning meets the thermal requirements listed in the Environmental Specifications.
-
Ensure that the cabinet or rack meets the requirements listed in the Rack Requirements.
-
Ensure that the site power meets the power requirements listed in the Power Specifications. If available, you can use an uninterruptible power supply (UPS) to protect against power failures.
Rack Requirements
The rack must be of the following type:
-
A standard 19-in. (48.3-cm) wide, four-post EIA rack, with mounting posts that conform to English universal hole spacing, per section 1 of ANSI/EIA-310-D-1992.
-
The rack-post holes can be square 0.38-inch (9.6 mm), round 0.28-inch (7.1 mm), #12-24 UNC, or #10-32 UNC when you use the Cisco-supplied slide rails.
-
The minimum vertical rack space per Cisco CSP 5400 must be two rack units (RUs), equal to 3.5 in. (88.9 mm).
Supported Cisco Slide Rail Kits
The Cisco CSP 5400 supports the following rail kit:
The ball-bearing slide rail kit is included with server.
Rack Installation Tools Required
The included slide rails for this Cisco CSP 5400 do not require tools for installation.